VBT-75 Vacuum Bottle Tester
----------部分中文介绍产品已停产或参数有变更,内容仅供参考。

VBT-75

Vacuum Bottle Tester

9115-UC [VBT-75]

The VBT-75 is a microprocessor-based, portable, 75kV dc vacuum bottle tester. This lightweight, portable tester is designed for testing circuit-breaker vacuum bottles in the field and at the shop.
Test voltages can be selected from 10 kV dc to 75 kV dc in 5 kV steps. The high-voltage test time can be set from 5 seconds to 2 minutes. The test voltage is raised to the selected voltage and held for the test time duration. After the test time duration has elapsed and the leakage current did not pass the preset value of 100 μA, 200 μA, or 300 μA, the test voltage is returned to zero and a "Pass" message is displayed. If a flash-over condition occurs, such as bottle failure, the test voltage is immediately turned off, a “Failure” message is displayed on the LCD screen, and the “TEST FAIL” LED light on the unit is also illuminated.
The presence of high voltage is indicated by an audible tone and an illuminated “HIGH VOLTAGE” LED light. For additional operator safety, an “ARM” switch must be held down during testing.
The VBT-75 features a back-lit LCD screen (16 characters by 2 lines) that is viewable in both bright sunlight and low-light levels. A turn-and-press knob is used to control the unit. An RS-232C interface port is provided for factory calibration and diagnostic testing.
The VBT-75 is furnished with a 10-foot test cable that is terminated with a quick-disconnect test clip. A transportation case is also included.

  • Automatic testing
  • 10 kV - 75 kV DC output in 5 kV steps
  • Selectable test time duration from 5 seconds to 2 minutes
  • Digital voltage and current display
  • Failure indicator LED
  • Very lightweight (10 lbs./4.53 Kg)
       

VBT-75

Cables

 
       
       

VBT-75

Technical Specifications

 
       
PHYSICAL SPECIFICATIONS Dimensions: 17”W x 10.5”H x 6.5” D (42.7 cm x 26.9 cm x 16.5 cm)
Weight: 10 lbs. (4.53 Kg)
INPUT POWER 90 - 240 Vac, 2A, 50/60 Hz
OUTPUT VOLTAGE 10kV - 75 kV dc in 5 kV steps; accuracy: 1.5%
OUTPUT  RIPPLE VOLTAGE 3% max
DISCHARGE TIME maximum discharge time for internal high voltage is 3 seconds
DISPLAY back-lit LCD (16 characters x 2 lines); viewable in bright sunlight and low-light levels
FAILURE INDICATOR failure indicator LED illuminates when test current exceeds 100 μA, 200 μA, 300 μA (programmable)
CONTROL single turn-and-press knob
TEMPERATURE Operating: -10°C to +50°C (+15°F to +122°F)
Storage: -30°C to +70°C (-22°F to +158°F)
HUMIDITY 90% RH @ 40°C (104°F) non-condensing
ALTITUDE 2,000 m (6,562 ft) to full safety specifications
CABLES one 10-foot (3.05m) high-voltage cable, one 10-foot (3.05m) high voltage return cable, one ground cable, one power cord
FURNISHED ACCESSORIES shipping case is included
WARRANTY one year on parts and labor
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
Last updated on March 18, 2015