TYPE |
Portable current transformer test set |
PHYSICAL SPECIFICATIONS |
16.8”W x 12.6”H x 12”D (42.7 cm x 32 cm x 26.9 cm); Weight: 55 lbs (25 kg) |
INPUT POWER |
100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50 Hz/60 Hz |
MEASUREMENT METHOD |
|
OUTPUT TEST VOLTAGES |
0 – 50 Vac @ 10A max, 0 – 250 Vac @ 10A max 0 – 500 Vac @ 5A max, 0 – 1500 Vac @ 1.2A max |
VOLTAGE READING RANGE |
0 – 2,200 Vac; Accuracy: ±1.0% of reading, ±1 volt |
CURRENT READING RANGE |
0 – 10A; Accuracy: ±1.0% of reading, ±0.02A |
CURRENT-RATIO RANGE |
0.8 – 999: 0.1%, 1000 – 1999: 0.3%, 2000 – 5000: 1% |
PHASE ANGLE MEASUREMENT |
0 - 360 degrees; Accuracy: ±1.0 degree |
DISPLAY |
Back-lit LCD Screen (240 x 128 dot graphic; 114mm x 64mm); viewable in bright sunlight and low-light levels |
PRINTER |
Built-in 4.5-inch wide thermal printer |
COMPUTER INTERFACES |
One RS-232C port (115k baud), one USB port |
EXTERNAL DATA STORAGE |
One USB Flash drive interface port (Flash drive not included) |
PC SOFTWARE |
Windows? XP/Vista-based CT Analysis software is included with purchase price |
INTERNAL TEST RECORD STORAGE |
Stores 140 test records. Each test record may contain up to 10 sets of excitation, resistance and ratio data |
INTERNAL TEST PLAN STORAGE |
Stores 128 test plans. Each test plan can store 10 excitation test voltage and current settings |
SAFETY |
|
ENVIRONMENT |
Operating: -10? to 50? C (15?F to +122? F); Storage: -30? C to 70? C (-22?F to +158? F) |
CABLES |
Two 20-foot X cable sets, One 35-foot H cable set, power cord, One cable-carrying duffel bag |
WARRANTY |
One year on parts and labor |
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F). Last updated on February 10, 2010 |