EZCT-2000A Current Transformer Test Set
----------部分中文介绍产品已停产或参数有变更,内容仅供参考。

EZCT-2000C Plus

Current Transformer Test Set

 
       
9101-UC [110V]
9102-UC [220V]
9019-SC [Shipping Case]

The EZCT-2000C Plus is Vanguard’s third-generation microprocessor-based current transformer test set. Designed specifically for CT testing, the EZCT-2000C Plus has the following outstanding features that can greatly increase productivity and save time during the commissioning stage:

  • Performs CT excitation, current-ratio, polarity, and phase angle tests
  • Measures insulation resistance and winding resistance of the CT secondary windings
  • Measures the CT’s load burden
  • Standalone or computer-controlled via USB or Bluetooth wireless interface

The EZCT-2000C Plus’ test leads can be connected to all the CT output terminals, and the complete CT test can be performed automatically without any operator intervention.

  • Performs CT excitation, current-ratio, polarity, and phase angle tests
  • Measures insulation resistance and winding resistance of the CT seconday windings
  • Measures the CT's secondary burden
  • Test record header information including company, substation name, circuit ID, manufacturer, CT serial number, operator name, and test record-comments
  • Built-in 4.5-inch wide thermal printer
  • Plot Multiple Saturation Curves
  • Stores up to 128 CT test plans and 140 test records internally
  • USB, Bluetooth, and USB Flash drive interface
&bbsp;      

EZCT-2000C Plus

Cables

 
       
       

EZCT-2000C Plus

Technical Specifications

 
       
TYPE Portable current-transformer test set
PHYSICAL SPECIFICATIONS 19"W x 13"H x 16"D (48.3 cm x 33cm x 40.1 cm); Weight: 73 lbs (33.1 kg)
INPUT POWER 100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz
MEASUREMENT METHOD and standards
 TEST OUTPUT VOLTAGES 0 – 50 Vac @ 10A max; 0 – 300 Vac @ 10A max; 0 – 500 Vac @ 5A max;
0 – 1200 Vac @ 1.2A max; 0 – 2000 Vac @ 1A max
CURRENT SOURCE 1 – 20A @ 0 – 15 Vac
CURRENT SOURCE DISPLAY Test current and current on-time
VOLTAGE READING RANGE 0 – 2,200 Vac; Accuracy: ±1.0% of reading, ±1 V
CURRENT READING RANGE 0 – 10A; Accuracy: ±1.0% of reading, ±0.02A
CT CURRENT RATIO RANGE 0.8 – 999: 0.1%; 1000 – 1999: 0.3%; 2,000 – 5,000: 1%
PHASE ANGLE MEASUREMENT 0 – 360 degrees; Accuracy: ± 1.0 degree)
RESISTANCE READING RANGE 100 micro-ohms – 10 ohms; Accuracy: 2% of reading, ± 1 count, ± 10 micro-ohms
INSULATION RESISTANCE READING RANGE 2 Mega-ohms – 500 Mega-ohms; Accuracy: 3% of reading, 500 – 1000 Vdc test voltage
DISPLAY Back-lit LCD Screen
240 x 128 pixels; 114mm x 64mm
Viewable in bright sunlight and low-light levels
PRINTER Built-in 4.5-inch wide thermal printer
COMPUTER INTERFACES One USB port and Bluetooth wireleass interface
EXTERNAL DATA STORAGE One USB Flash drive interface port (Flash drive not included)
PC SOFTWARE Windows?-based CT Analysis software is included with purchase price
INTERNAL TEST RECORD STORAGE Stores 140 test records. Each test record may contain up to 10 sets of excitation, resistance and ratio data
INTERNAL TEST PLAN STORAGE Stores 128 test plans. Each test plan can store 10 excitation test voltage and current settings
SAFETY
ENVIRONMENT Operating: -10°C to +50°C (+15°F to +122°F);
Storage: -30°C to +70°C (-22°F to +158°F)
HUMIDITY 90% RH @ 40°C (104°F) non-condensing
ALTITUDE 2,000 m (6,562 ft) to full safety specifications
CABLES One 20-foot cable set (X1-X5), one 35-foot H cable set, current source cables, insulation test cables, power cord, ground cable. A transportation case is included with the purchase price
WARRANTY One year on parts and labor
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
Last updated on July 19, 2013