TYPE |
portable digital circuit breaker analyzer |
PHYSICAL SPECIFICATIONS |
18.5”W x 14”H x 7”D (47.0 cm x 35.7 cm x 17.6 cm);
Weight: 20 lbs (9.1 kg) |
INPUT POWER |
3 Amps, 100 – 240 Vac, 50/60 Hz |
DRY-CONTACT INPUTS |
3 dry-contact channels; each channel detects main contact and insertion resistor contact |
TIMING WINDOWS |
1-second, 10-seconds, or 20-seconds |
TIMING RESOLUTIONS |
±50 micro-seconds @ 1-second duration, ±500 micro-seconds @ 10-second duration, ±1.00 milli-second @ 20-second duration |
TIMING ACCURACY |
0.05% of reading ±0.1 ms @ 1-second duration |
CONTACT DETECTION RANGE |
Closed: less than 20 ohms; Open: greater than 5,000 ohm |
RESISTOR DETECTION RANGE |
50 – 5,000 ohms |
TRIGGER INPUT VOLTAGE |
Open/Close: 30 – 300V, DC or peak AC |
VOLTAGE SENSING INPUT RANGE |
V1: analog input; 0 – 255V, DC or peak AC; Sensitivity: ±1V
V2: voltage presence/absence detector input; 30 – 300V, DC or peak AC |
BREAKER OPERATIONS |
Initiate Open, Close, Open – Close, Close – Open, Open – Close – Open |
BREAKER INITIATE CAPACITY |
30A, 250 Vac/dc max |
INITIATE CURRENT READING RANGE |
One, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5Khz |
TRAVEL TRANSDUCER INPUT |
1 digital travel transducer channel; Linear range: 0.0 – 60.0 in (±0.005 in.); Rotary range: 0 – 360 degrees (±0.006 degrees) |
CONTACT TRAVEL POINT DIFFERENCE |
Measures “slow-close” contact-point distances; results can be printed |
CT CURRENT SENSOR |
One, non-contact, 0 – 100A |
DISPLAY |
Back-lit LCD screen (240 x 128 pixels); viewable in bright sunlight and low light levels |
PRINTER |
Built-in 4.5-inch wide thermal printer can print both graphic contact travel waveforms and tabulated test results |
INTERNAL TEST RECORD STORAGE |
Stores up to 200 test records and 100 test plans |
COMPUTER INTERFACES |
One USB port, optional Bluetooth interface |
PC SOFTWARE |
Windows-based Vanguard Circuit Breaker Analysis (VCBA S2) software is included with purchase price. Software updates available at no additional charge. |
SAFETY |
|
ENVIRONMENT |
Operating: -10°C to 50° C (15°F to +122° F); Storage: -30° C to 70° C (-22°F to +158° F) |
OPTIONS |
Transportation case (available for the DigiTMR S2 and the travel transducers) |
WARRANTY |
One year on parts and labor |