TYPE |
Portable current-transformer test set |
PHYSICAL SPECIFICATIONS |
19”W X 13”H x 15.8” D (48.3 cm x 33.0 cm x 40.1 cm); Weight: 73 lbs (33.1 kg) |
INPUT POWER |
100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz |
MEASUREMENT METHOD |
|
TEST OUTPUT VOLTAGES |
0 – 50 Vac @ 10A max; 0 – 300 Vac @ 10A max; 0 – 500 Vac @ 5A max; 0 – 1200 Vac @ 1.2A max; 0 – 2000 Vac @ 1A max |
CURRENT SOURCE |
1 – 20A @ 0 – 15 Vac |
CURRENT SOURCE DISPLAY |
Test current and current on-time |
VOLTAGEREADING RANGE |
0 – 2,200 Vac; Accuracy: ±1.0% of reading, ±1 V |
CURRENTREADING RANGE |
0 – 10A; Accuracy: ±1.0% of reading, ±0.02A |
CT CURRENT RATIO RANGE |
0.8 – 999: 0.1%; 1000 – 1999: 0.3%; 2,000 – 5,000: 1% |
PHASE ANGLE MEASUREMENT |
0 – 360 degrees; Accuracy: ± 1.0 degree) |
RESISTANCEREADING RANGE |
100 micro-ohms – 10 ohms; Accuracy: 2% of reading, ± 1 count |
INSULATIONRESISTANCE READING RANGE |
2 Mega-ohms – 500 Mega-ohms; Accuracy: 3% of reading, 500 – 1000 Vdc test voltage |
DISPLAY |
Back-lit LCD Screen
240 x 128 dot graphic; 114mm x 64mm
Viewable in bright sunlight and low-light levels |
PRINTER |
Built-in 4.5-inch wide thermal printer |
COMPUTER INTERFACES |
One RS-232C (115,000 Baud) port, One USB port |
EXTERNAL DATA STORAGE |
One USB Flash drive interface port |
PC SOFTWARE |
Windows XP/Vista-based CT Analysis software is included with the purchase price |
INTERNAL TEST RECORD STORAGE |
Stores 140 test records. Each test record may contain up to 10 saturation curves, current-ratio readings, and polarity and DC resistance readings |
INTERNAL TEST PLAN STORAGE |
Stores 128 test plans. A test plan consists of the saturation test voltage, current selection, CT nameplate ratios, and CT winding terminal combinations (X1 to X5) for each test |
SAFETY |
|
ENVIRONMENT |
Operating: -10°C to 50°C (15°F to +122°F); Storage: -30°C to 70°C (-22°F to +158°F) |
CABLES |
Five 20-foot X cable sets, One 35-foot H cable set, current source cables, insulation test cables, power cord, ground cable. A transportation case is included with the purchase price. |
WARRANTY |
One year on parts and labor |
Specifications are valid at nominal voltage and ambient temperature of +25C (+77F).
Last updated on March 16, 2009 |